Item
Mode
Program run mode
Constant value control
mode
Control section
PID control
Normal reverse operation selection
Programmer function
Output section
Auxiliary output
Current output (5G)
Auxiliary output CH1, CH2
READY
: Preparation state (control stop, select of program number is possible.)
RUN
: Advancing run state
HOLD
: Hold run state
FAST
: Fast feed run state
END
: End point run state
READY FAST
: Preparation and the fast feed state
AUTO
: Automatic run state
MANUAL
: Manual run state (output is operatable to console)
READY
: Preparation state (control stop)
RUN
: Run state
AUTO
: Automatic run state
MANUAL
: Manual run state (Enables manual output from system console.)
Proportional band (P)
0.0 to 1000.0% (0.0: On-off control)
Integral time (I)
0 to 3600s (0: PD control)
Derivative time (D)
0 to 1200s (0: PI control)
Manipulated variable
Low-limit : –5.0% to high-limit
limit
High-limit : Low-limit to +105.0%
Manual reset
0.0 to 100.0%
No. of PID groups
16 groups for program operation (9 segment specific
and 7 automatic zone selecting)
PID groups selection
Segment specified, automatic zone selectable during
program run
Manipulated variable change 0.1 to 110.0%/0.1s
Auto tuning
Automatic setting of PID value by limit cycle method
On-off control differential
0 to 1000U
Selection is settable
Selection
Manipulated variable output is selectable to SP output
Scaling
Possible
Output resolution
1/10000
Type
PV, SP, deviation, MV, PV1, PV2
Scaling
Possible
Output current
: 4 to 20mA dc
Allowable load resistance
: Lower than 600 (under operating conditions)
: Lower than
Output accuracy
: 1/10000
Output resolution
Max. output current
: 21.6mA dc
Min. output current
: 2.4mA dc
Output update cycle
: 0.1s
: Lower than 25V
Open time terminal voltage
Chapter 11. SPECIFICATIONS
Specifications
0.1% FS (under the standard conditions)
11-3

Hide quick links: