Chapter 11. SPECIFICATIONS
Item
Input section
Cold junction compensation system
Scaling
Root extraction
PV equalizer
(linearization)
Input bias
Digital filter
External switch
Number of input point
input section
Connectable output type
Open terminal voltage
Terminal current in case of short circuit
Allowable contact resistance
(no-voltage contact)
Allowable residual current
(open collector ON)
Leakage current
(open collector OFF)
Allocation (fixed)
Allocation (variable)
Input sampling cycle
On detection Min. hold time
Display and
Display panel 1
setting section
Display panel 2
Program number display
Segment number display
Message display panel
Profile display
Each status display
Operating keys
Loader connection port
* : available on the DCP551E***** model only
11-2
Internal or external compensation (at 0 C) selectable
-19999 to +20000U (Only linear input can sets. Reverse scaling and optional decimal point position can set.)
Drop out 0.2 to 10.0%. It is possible to set DC current and DC voltage range.
PV1: 9 broken line (setting to 10 point)
PV2: 19 broken line (setting to 20 point)
-1000 to +1000U variable
0.0 to 120.0sec variable (0.0: Filter off)
16 points
No-voltage contact (relay contact), and open corrector (sink current toward 0V)
8.5V
0.5V during common terminal ((12) and (40) terminals) and every input
terminal (under operating conditions)
Current to run every terminal is about 6mA (under operating conditions)
On condition: Lower than 250
Off condition: Higher than 100 k
Lower than 2V (under operating conditions)
Lower than 0.1mA (under operating conditions)
RUN, HOLD, RESET, ADV, program number
RAMP-E, FAST, AT, AUTO/MANUAL, G.SOAK reset, forward-reverse operation,
auto load* , PV1/2 selection
0.1s
0.2s (program number is 0.4s)
Digital 5 digits, 7 segments, green color
Indicates PV and other data on basic display status, indicates an item code on parameter setting status.
Digital 5 digits, 7 segments, orange color
Indicates SP, output %, and other data on basic display status, indicates a set point of item on parameter setting status.
Digital 2 digits, 7 segments, green color
Indicates a program number on basic display status.
Digital 2 digits, 7 segments, green color
Indicates a segment number on basic display status, indicates a item number on parameter setting status.
Indicates an alarm code number when an alarm occurs.
Indicates output graph, deviation graph, event status, program tag, and other data on basic display status,
Indicates a reference message on parameter setting and program setting.
Indicates a operation contents and operation result on memory card operation.
7 flat LED, orange color
Indicates the rising, soaking, and falling tendencies of program pattern.
22 flat LED
Mode
: RUN, HLD, MAN, PRG (green color)
Display contents: PV, SP, OUT, TM, CYC, SYN, DEV (green color)
Battery voltage : BAT (red color) (flickers when the battery voltage has dropped.)
Status
: AT (green color)
Event
: EG1, EG2 (red color)
18 rubber keys (DCP551E***** model), 16 ruber keys (DCP551F***** model)
1 (Using exclusive connection cable, stereo pin jack)
Specifications
(under operating conditions)
(under operating conditions)