DCP551 Parameter Work Sheet
No.
Item code
PA 41
41
EG1 LED display event number
PA 42
42
EG2 LED display event number
PA 43
43
PID operation initialize
PA 46
46
G.SOAK time
PA 51
51
PV1 equalizer compensation point No. 1
PA 52
52
PV1 equalizer compensation amount No. 1 0 PVU
PA 53
53
PV1 equalizer compensation point No. 2 500 PVU
PA 54
54
PV1 equalizer compensation amount No. 2 0 PVU
PA 55
55
PV1 equalizer compensation point No. 3 1000 PVU
PA 56
56
PV1 equalizer compensation amount No. 3 0 PVU
PA 57
57
PV1 equalizer compensation point No. 4 1500 PVU
PA 58
58
PV1 equalizer compensation amount No. 4 0 PVU
PA 59
59
PV1 equalizer compensation point No. 5 2000 PVU
PA 60
60
PV1 equalizer compensation amount No. 5 0 PVU
PA 61
61
PV1 equalizer compensation point No. 6 2500 PVU
PA 62
62
PV1 equalizer compensation amount No. 6 0 PVU
PA 63
63
PV1 equalizer compensation point No. 7 3000 PVU
PA 64
64
PV1 equalizer compensation amount No. 7 0 PVU
PA 65
65
PV1 equalizer compensation point No. 8 3500 PVU
PA 66
66
PV1 equalizer compensation amount No. 8 0 PVU
PA 67
67
PV1 equalizer compensation point No. 9 4000 PVU
PA 68
68
PV1 equalizer compensation amount No. 9 0 PVU
PA 69
69
PV1 equalizer compensation point No. 10
PA 70
70
PV1 equalizer compensation amount No. 10 0 PVU
PA 71
71
PV2 equalizer compensation point No. 1
PA 72
72
PV2 equalizer compensation amount No. 1 0 PVU
PA 73
73
PV2 equalizer compensation point No. 2 500 PVU
PA 74
74
PV2 equalizer compensation amount No. 2 0 PVU
PA 75
75
PV2 equalizer compensation point No. 3 1000 PVU
PA 76
76
PV2 equalizer compensation amount No. 3 0 PVU
PA 77
77
PV2 equalizer compensation point No. 4 1500 PVU
PA 78
78
PV2 equalizer compensation amount No. 4 0 PVU
PA 79
79
PV2 equalizer compensation point No. 5 2000 PVU
PA 80
80
PV2 equalizer compensation amount No. 5 0 PVU
PA 81
81
PV2 equalizer compensation point No. 6 2500 PVU
PA 82
82
PV2 equalizer compensation amount No. 6 0 PVU
PA 83
83
PV2 equalizer compensation point No. 7 3000 PVU
PA 84
84
PV2 equalizer compensation amount No. 7 0 PVU
PA 85
85
PV2 equalizer compensation point No. 8 3500 PVU
PA 86
86
PV2 equalizer compensation amount No. 8 0 PVU
PA 87
87
PV2 equalizer compensation point No. 9 4000 PVU
denotes items settable only on models with two PV input channels.
2
Item
Factory default
settings
0
0
0
2.0
Range lower
limit value
Range upper
limit value
Low-limit value
of range
User
Settings and descriptions
-
settings
0 to 16
(0: EG1 LED is off.)
0 to 16
(0: EG2 LED is off.)
0 : No initialization during advance processing and PID group change
1 : Initializes during advance processing but not during
PID group change.
2 : No initialization during advance processing but
initializes during PID group change.
3 : Initializes both during advance processing and PID group change.
0.1 to 60.0sec
PV1 range lower limit value (tied)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
–19999 to +20000 PVU(PV1)
–1000 to +1000 PVU(PV1)
PV1 range upper limit value (tied)
–1000 to +1000 PVU(PV1)
PV2 range lower limit value (tied)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)
–1000 to +1000 PVU(PV2)
–19999 to +20000 PVU(PV2)