Tip
Note that the net tag names provided in the above example are used for illustration purposes only. You can use
different net tag names as required.
5
Click Apply.
Click OK.
6
Configuring field network tag names for the AS-i Link/AS-i Link Advanced devices
1
Click the Process Data menu in the Navigation Area.
2
Click
to view the input and output modules associated with the AS-i Link/AS-i Link Advanced device.
3
Modify the net tag names for a single byte of data. This tag name must refer to the entire 4 byte area with the
tag name referring to its own byte plus the 3 byte with the default names.
In the above figure, net tag "Slv1_7Out" refers to its own byte, plus the 3 bytes with the default names
"Output_2," "Output_3," and "Output_4."
Similarly, the net tag "Slv16_23In" refers to its own byte, plus the 3 bytes with the default names
"Input_10," "Input_11," and "Input_12."
Tip
Note that the net tag names provided in the above example are used for illustration purposes only. You can use
different net tag names as required.
4
Click Apply.
Click OK.
5
6 PROTOCOL BLOCK
75