5.6.6 PGM redundancy notifications

The following table lists the redundancy-related notifications implemented for the PGM that may occur during
controller synchronization and switchover operations.
Notification
Backup State
Redun Incompatible Partner
Redun No Partner
Redun Non-Redundant
Redun Partner Visible on
FTE
Redun Partner Visible on
Redun Link
Redun Sync In Progress
Redun Sync Maintenance
Redundancy Link Active
Redundancy Link Inactive
Switchover
Generated when...
The secondary PGM is successfully restarted.
The redundancy cable of the primary PGM is connected to a different PGM.
Both the primary and the secondary PGM generate this notification when the partner is not
present.
Both FTE cables of the PGM configured explicitly as non-redundant are removed and re-
connected after sometime.
Both FTE cables of the secondary PGM are removed and re-connected after sometime.
Both the primary and the secondary PGM generate this notification upon detecting a
compatible partner visible across the redundancy private path.
Both the primary and the secondary PGM generate this notification after both FTE cables
are removed and re-connected and the initial synchronization is started.
Both the primary and the secondary PGM generate this notification after completing the
initial synchronization.
This notification is generated when the redundancy link cable is connected.
This notification is generated when the redundancy link cable is disconnected.
Both the primary and the secondary PGM generate this notification when a switchover is
initiated by entering the switchover command.
5 PROFIBUS GATEWAY MODULE (PGM) BLOCK
47