7.7 CEAG Device Support Block (CEAGDSB)

The CEAGDSB runs on the PGM and represents one PROFIBUS field device in the PROFIBUS network. The
CEAGDSB processes the raw data from the CEAG field devices and converts it to the PDC format supported
by Experion. The CEAGDSB communicates with the master PGM for data conversion.
A single CEAGDSB supports up to 46 I/O modules. The CEAGDSB is used for configuring the CEAG LB/FB
Remote I/O family when using PROFIBUS communication unit Easy COM LB8106/FB8206 V6.XX.
The CEAGDSB supports the I/O stations per bus line that provide 31 stations without repeaters and up to 125
stations with repeaters. The maximum number of modules per slave device is 49 (46 I/O modules plus 3 slots
reserved for the communication unit) in the field network configuration. The communication unit present in
each station transfers the data of internal system bus to the protocols of the master bus system.
The maximum number of PDCs required per station is 48 and this can be interpreted as follows:
2 PDCs for the communication unit and 46 PDCs for 46 one-channel modules.
Or
2 PDCs for the communication unit and 46 PDCs for 23 multi-channel modules having both inputs and
outputs.
Attention
The maximum number of one-channel I/O module per station is 46.
The maximum number of multi-channel I/O module per station is 23.
Related topics
"Device Support Block (DSB) overview" on page 112
"Generic Drive Device Support Block (DRIVEDSB)" on page 124
"Generic Device Support Blocks (GENPADSB and GENPAGWDSB) for PA devices" on page 122
"Siemens AS-i Link Device Support Block (Siemens DP/AS-i-Link DSB)" on page 134
"Siemens ET200M Device Support Block (Siemens ET200M DSB)" on page 138
"Turck Excom Device Support Block (Turck Excom DSB)" on page 142
"Generic Device Support Blocks (GENDSB and GENIODSB)" on page 120

7.7.1 I/O modules supported by the CEAGDSB

The following tables lists the I/O modules supported by the CEAGDSB.
CEAGDSB
PDC Type
Digital Input with line fault detection - 2 channels
Digital Input with line fault detection - 3 channels
7 DEVICE SUPPORT BLOCK (DSB)
Supported CEAG modules
LB1101
LB1001
FB1201
FB1301
LB1102
LB1002
FB1202
FB1302
2xxx
129