Profibus gateway module
Hide thumbs Also See for Experion PKS:
Table of Contents

Advertisement

DSB
Input side behavior
The DSB is informed of the communication loss.
The status of the PDCs are set to "Device
communication error."
The data is set to fail-safe values.
The PDC channel status is set to "Bad_ConnError."
Output side behavior
The fail-safe value of the device is set on the DSB
block.

13.1.3 Loss of communication between the PGM and control strategies

The control strategies can lose communication with the PGM due to any of the following conditions.
Removal of the PGM module.
Removal of the FTE cable from the PGM.
Removal and re-insertion of the slave devices.
In any of the above scenarios, the control strategies using the PROFIBUS data go into fail-safe data.

13.1.4 CEEC300 state is changed to Idle

When the CEESTATE parameter of the C300 is changed to "Idle," the PGM operates as follows:
The PGM continues to operate as it was prior to this change and publishes the new data to the C300
Controller.
The PIOMB continues to execute since IOMs continue to execute even when CEE is "Idle."
The input channels are set to fail-safe values (NaN and Off for analog and digital values respectively). The
input channel status is set to "Bad."
The output channel status is set to "Bad."
The output of PROFIBUS slave devices hold the last good value when the CEE is "Idle."

13.1.5 Inactivation of PIOMB

When a PIOMB associated with a PDC is inactivated, the PGM operates as follows:
Input side behavior - The PGM continues to operate as it was prior to the inactivation and publishes data to
the C300 controller.
Output side behavior - The output of the PROFIBUS slave devices hold the last value until they receive a
new value.

13.1.6 Deletion of PIOMB

When a PIOMB associated with a PDC is deleted, the PGM operates as follows:
Input side behavior - The PGM continues to operate as it was prior to the deletion and publishes data to the
C300. However, the PGM stops publishing the data after the PIOMB closes the connection to its associated
PDC.
Output side behavior - The PGM stops receiving output publications from the PIOMB after it closes the
connection to its associated PDC. The output of the analog devices and digital devices are initialized to 0
and 0% respectively.
13 PROFIBUS GATEWAY MODULE (PGM) TROUBLESHOOTING
PIOMB
Input type PIOMB
The PIOMB receives the "Communication Fail" status and
the channel will follow that status.
Input Channels will be set to fail-safe values (NaN and OFF
for analog and digital values respectively).
Channel value status is set to "Bad."
Output type PIOMB
The PIOMB receives the "Communication Fail" status and
the output channel blocks follow that status.
Channel value status is set to "Bad."
251