In the Device Type box, type the description of the device type.
12
In the Connection Break TimeOut (Sec) box, type the duration in seconds during which the network
communication break needs to be filtered off.
If the communication break condition persists even after this time, then the status of the slave device is set to
"Communication Error." This parameter is applicable only when the slave device is disconnected from the
Profibus network. If the complete Profibus network is down, the status of all slave devices is set to
"Communication Error" immediately.
Select the Connection Break Timeout applicable for Network Down check box if you want the output
13
channels to initialize back from the user-defined values after the connection break timeout timer is exceeded.
If the complete Profibus network is down and you have not selected this check box, the status of all slave
devices is set to "Communication Error" immediately.
However, if you have selected this check box and the complete Profibus network is down, the status of all
slave devices are set to "Communication Error" after the connection break timeout is exceeded.
14
Select the Reset counters check box if you want to reset all static counters.
Tip
The RESETCOUNTER parameter is not applicable to the Siemens AS-I DSB, Turck Excom DSB, and Siemens
ET200M DSB.
In the Vendor Name list, select the vendor name.
15
Tip
The Vendor Name box is applicable only to the DRIVEDSB.
In the Drive Control Mode list, select the control mode of the drive. You can select the following control
16
modes.
SpeedControlMode
PositioningMode
Attention
Note that changing the control mode from the Control Builder configuration does not impact the drive's
runtime. However, it only changes the descriptions/meanings of the Control Word and Status Word bits.
The CONTROLMODE parameter is a configuration only parameter and cannot be changed after the DSB is
loaded. For more information on the CONTROLMODE parameter, refer to the PROFIBUS Gateway Module
Parameter Reference Guide.
Tip
The Drive Control Mode box is applicable only to the DRIVEDSB.
Click the Slave Status tab.
17
Attention
The Slave Status tab displays the slave communication standard status bits and extended diagnostic information in
the Monitoring view.
18
Click the Alarms tab.
The Alarms tab is only applicable to the GENDSB and the DRIVEDSB as you can configure alarms only
for these DSBs.
19
Click the PDC tab.
Attention
The PDC tab of the DSB block is used for defining the PDCs. You cannot proceed with the DSB configuration
until you complete the PDC configuration. To configure the PDCs, see section Configuring the PDC tab.
Use the online help as a guide to complete the configuration entries on all other tabs.
20
21
Click OK.
7 DEVICE SUPPORT BLOCK (DSB)
151