7.16.4 CEAG DSB specific PDC configuration guidelines

The following list summarizes the CEAG DSB specific PDC configuration guidelines that you must remember
while configuring the CEAG DSB PDC.
The number of PDCs supported by CEAGDSB is 24.
In the Number of Channel column, the number of channels are automatically updated based on the PDC
type.
In the Channel Number column, the channel number is automatically updated based on the number of
channels configured for the selected module.
For example, if the number of channels configured for a module is 4, then this column lists the channel
numbers as 0, 1, 2, and 3.
In the Channel Type column, the channel type is automatically set based on the PDC type.
In the Channel Data Type column, the channel data type is automatically set based on the PDC type.
With R410, you can modify the values of the following parameters even after a PDC is associated and
connected to a PIOMB. However, you must ensure that you reload both the DSB and the PIOMB after
modifying the parameter value. If you do not reload both the DSB and the PIOMB, there may be a break in
the connection between the DSB and the PIOMB.
– Channel Description (CHDESCRIPTION)
– Channel Low Range (CHLOWRANGE)
– Channel High Range (CHHIGHRANGE)
Applicable
Description
for
Input
When you select this option, the status is read from raw data and channel status is
channels
updated. The channel's Status column and the PA Status column display the actual
device status.
The Update channel status option is selected by default.
Input
When you select this option, the status is read from raw data. The Status column and the
channels
PA Status column display the actual device status. In addition, an alarm Data status
below limit in PDC is reported if the status is below the defined first acceptable PA
status value.
Attention
You must define the first acceptable PA status value while configuring the DSB
(GENPADSB/GENPAGWDSB) for the alarms to be reported when the channel
status is below the first acceptable PA status value.
Output
When you select this option, the channel status is always set to GoodCasc_NonSpecific.
channels
However, the PA Status column displays the value Not Applicable. If the PA device is
removed from the network, the PA Status column displays the value Not Available.
The Set output status option is selected by default.
Attention
For GENPAGWDSB, the configurable output channel status is always set to
GoodCas_NonSpecific even in the absence of the device. However, the extended
diagnosis reports the device unavailability. With the extended diagnosis and the
user-defined alarms, you can set the PDC channel state to Bad_NonSpecific for
that specific channel.