About Auto-Discovery Of Hart Devices - Honeywell Experion PKS User Manual

Profibus gateway module
Hide thumbs Also See for Experion PKS:
Table of Contents

Advertisement

HART Devices table
The HART Devices table provides information about the following parameters.
Tag (HTAG) name of the HART devices
Manufacturer (HDEVMFG) name of the HART device
Type (HDEVTYPENAME) name of the HART device
Type (HDEVTYPE) of the HART device
Revision (HDEVREV)of the HART device
Id (Serial Number) (HDEVID) of the HART device
Device Extended High Range (URL) of the HART device
Device High Range (URV) of the HART device
Device Low Range (LRV) of the HART device
Device Extended Low Range (LRL) of the HART device
Scan Priority for HART Variables (HSCANCFG) of the HART device
Scan Priority for Command (HSCANCFGC48) of the HART device

8.5.3 About auto-discovery of HART devices

The PBHIOMB block enables you to find the HART devices that are connected to the HART IO module. The
auto-discovery of the HART devices can be performed only when the loaded PBHIOMB have some channels
(PBHCHANNEL) that are not configured.
Attention
If all the channels in the PBHIOMB are configured, then the auto-discovery of HART devices is not possible.
You can use the Find HART Devices (FINDHDEVICES) parameter to discover the HART devices that are
connected to the HART IO module. The following figure displays the PBHIOMB configuration form when the
auto-discovery of HART devices is enabled.
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
199

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents