Viewing The Slave Device's Extended Diagnosis - Honeywell Experion PKS User Manual

Profibus gateway module
Hide thumbs Also See for Experion PKS:
Table of Contents

Advertisement

3
Right-click the slave device and select Diagnostic.
The Diagnostics configuration form appears. The Diagnosis menu in the Navigation Area is selected by
default.
Attention
Click OK.
4

6.11.7 Viewing the slave device's extended diagnosis

Perform the following steps to view the slave device's extended diagnosis
1
Navigate to the Field Network Configuration tab of the Protocol Block in which you have configured the
slave device and the master.
Right-click the slave device and select Connect.
2
Attention
You must right-click the slave device and select Disconnect to discontinue monitoring of the slave devices online.
The slave device appears highlighted as displayed in the following figure.
The Slave Device and the Watchdog On LEDs must be green during normal conditions.
If the slave device has extended diagnostics, the Extended Diagnostics LED appears red in color.
Similarly, the appropriate LEDs must appear in green based on the error condition.
6 PROTOCOL BLOCK
101