Note:
The parameter can only be set to the values 0, the value of the actual device topology, the value of the actual device
target topology and FFFFFFFF hex.
If the value 0 is displayed in all of the indices, then the system has still not been commissioned.
The value FFFFFFFF hex indicates that the topology was not generated by the automatic device configuration but
was commissioned using the commissioning software (e.g. using parameter download).
p0100
IEC/NEMA mot stds / IEC/NEMA mot stds
VECTOR_G
Can be changed: C2(1)
Data type: Integer16
P-Group: Converter
Not for motor type: FEM
Min
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
1:
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
p0316, r0333, r0334, p0341, p0344, r1493, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0336, r0337, p1800
Note:
The parameter can only be changed for vector control (p0107).
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
p0101[0...n]
Drive object numbers / DO numbers
CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Topology
CU_G150_PN
Not for motor type: -
Min
0
Description:
The parameter contains the object number via which every drive object can be addressed.
The number of an existing drive object is entered into each index.
Value = 0: No drive object is defined.
Note:
The numbers are automatically allocated.
For the commissioning software, this object number cannot be entered using the expert list, but is automatically
assigned when inserting an object.
r0102[0...1]
Number of drive objects / DO count
CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Topology
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the number of existing or existing and prepared drive objects.
Index:
[0] = Existing drive objects
[1] = Existing and prepared drive objects
Dependency:
Refer to: p0101
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
IEC-Motor (50 Hz, SI units)
NEMA motor (60 Hz, US units)
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
62
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
71