Bi: Tb30 Analog Inputs Invert Signal Source / Tb30 Ai Inv S S; Bi: Tm31 Analog Inputs Invert Signal Source / Tm31 Ai Inv S S; Tb30 Analog Inputs Noise Suppression Window / Tb30 Ai Window; Tm31 Analog Inputs Window To Suppress Noise / Tm31 Ai Window - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p4067[0...1]

BI: TB30 analog inputs invert signal source / TB30 AI inv s s

TB30
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Sets the signal source to invert the analog input signals of the Terminal Board 30 (TB30).
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
p4067[0...1]

BI: TM31 analog inputs invert signal source / TM31 AI inv s s

TM31
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Sets the signal source to invert the analog inputs signals of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4068[0...1]

TB30 analog inputs noise suppression window / TB30 AI window

TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.00 [%]
Description:
Sets the noise suppression window of the analog inputs for Terminal Board 30 (TB30).
Changes less than the window are suppressed.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
AI: Analog Input
p4068[0...1]

TM31 analog inputs window to suppress noise / TM31 AI window

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.00 [%]
Description:
Sets the noise suppression window of the analog inputs for Terminal Module31 (TM31).
Changes less than the window are suppressed.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
20.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
20.00 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 3
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
613