Bi: Infeed Operation / Inf Operation; Power Unit Main Contactor Holding Time After Off1 / Pu T_Mc After Off1 - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Bit field:
Bit
00
01
02
Dependency:
Refer to: p0864
Note:
Re bit 00:
Bit 0 signals that the infeed is ready.
When the operating signal is transferred via binector output r0863.0 this allows several drives to start (run-up)
staggered over time when they are simultaneously powered up.
To realize this, the following connections/interconnections are required:
Drive 1: Interconnect binector input p0864 with binector output r0863.0 of the infeed
Drive 2: Interconnect binector input p0864 with binector output r0863.0 of drive 1
Drive 3: Interconnect binector input p0864 with binector output r0863.0 of drive 2 etc.
The first drive only transfers the operating signal to the next drive after it has reached its ready condition.
Re bit 01:
Bit 1 is used to control an external line contactor.
Re bit 02:
This bit only signals line supply failure for Active Infeed (A_INF) and Smart Infeed (S_INF).
p0864

BI: Infeed operation / INF operation

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the operating signal of the infeed (e.g. BO: r0863.0).
Dependency:
Refer to: r0863
Note:
The sequence control of a servo/vector drive requires this signal.
The following applies for an infeed without DRIVE-CLiQ:
For these infeeds, the "ready" message is available via an output terminal. This signal must be connected to a digital
input. The drives supplied from this infeed must use this signal as ready signal (BI: p0864 = digital input).
p0867

Power unit main contactor holding time after OFF1 / PU t_MC after OFF1

VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the main contactor holding time after OFF1
Dependency:
Refer to: p0869
Note:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switch-on inhibit must be
acknowledged via the source of p0840 = 0 (OFF1) – and before the main contactor holding time expires, should go
back to 1, otherwise the main contactor will open.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Closed-loop control operation
Energize contactor
Infeed line supply failure
1 signal
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
500.0 [ms]
2 Parameters
2.2 List of parameters
0 signal
No
No
No
Access level: 2
Func. diagram: 2610, 8710,
8910
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50.0 [ms]
FP
2610,
8710,
8810,
8910
2610,
2634,
7990,
8734,
8834,
8934
-
263

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents