r0022

Speed actual value rpm smoothed / n_act rpm smooth

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [rpm]
Description:
Displays the smoothed actual value of the motor speed.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
For U/f control and when slip compensation is deactivated (see p1335), the synchronous speed to the output
frequency is shown in r0022.
Dependency:
Refer to: r0021, r0063
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
For U/f control, the mechanical speed calculated from the output frequency and the slip is shown in r0063[2] even if
slip compensation is deactivated.
r0024

Output frequency smoothed / f_outp smooth

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Hz]
Description:
Displays the smoothed converter frequency.
Dependency:
Refer to: r0066
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
r0025

CO: Output voltage smoothed / U_outp smooth

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Vrms]
Description:
Displays the smoothed output voltage of the power unit.
Dependency:
Refer to: r0072
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2000
Max
- [Hz]
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2001
Max
- [Vrms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6799
Unit selection: -
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 5300, 5730,
6300, 6799
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 2
Func. diagram: 5730, 6300,
6799
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
47