Co/Bo: Status Word Faults/Alarms 1 / Zsw Fault/Alarm 1; Hysteresis Speed 2 / N_Hysteresis 2 - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
13
14
15
Dependency:
Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
r2139.0...15

CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Display and BICO output for status word 1 of faults and alarms.
Bit field:
Bit
00
01
03
05
06
07
08
11
12
13
14
15
Note:
Re bit 03, 05, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present" or "alarm present" has occurred, a
change in the buffer was also detected (r0944, r9744, r2121).
Re bit 06, 08:
These status bits are used for internal diagnostic purposes only.
Re bit 12, 11:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes
only on certain automation systems with integrated SINAMICS functionality.
p2140[0...n]

Hysteresis speed 2 / n_hysteresis 2

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2155, r2197
514
External fault 1 (F07860) effective
External fault 2 (F07861) effective
External fault 3 (F07862) effective
Signal name
Being acknowledged
Acknowledgment required
Fault present
Safety message present
Internal message 1 present
Alarm present
Internal message 2 present
Alarm class bit 0
Alarm class bit 1
Maintenance required
Maintenance urgently required
Fault gone/can be acknowledged
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
High
High
Yes
Yes
Yes
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
300.00 [rpm]
List Manual (LH2), 04/2014, A5E03263479A
No
No
No
Access level: 2
Func. diagram: 2548
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
Low
Low
No
No
No
Access level: 3
Func. diagram: 8010
Unit selection: p0505
Expert list: 1
Factory setting
90.00 [rpm]
SINAMICS G130/G150
8060
8060
8060
FP
-
-
8060
-
-
8065
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents