Alarm Value / Alarm Value; Alarm Time Removed In Milliseconds / T_Alarm Res Ms; Change Acknowledge Mode Fault Number / Chng Ackn F_No; Change Acknowledge Mode Mode / Chng Ackn Mode - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r2124[0...63]

Alarm value / Alarm value

All objects
Can be changed: -
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays additional information about the active alarm (as integer number).
Dependency:
Refer to: r2110, r2122, r2123, r2125, r2134, r2145, r2146, r3121, r3123
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2125[0...63]

Alarm time removed in milliseconds / t_alarm res ms

All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2114, r2122, r2123, r2124, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
p2126[0...19]

Change acknowledge mode fault number / Chng ackn F_no

All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2127[0...19]

Change acknowledge mode mode / Chng ackn mode

All objects
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Not for motor type: -
Min
1
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
2:
3:
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
510
Acknowledgment only using POWER ON
Ack IMMEDIATELY after the fault cause has been removed
Acknowledgement only for PULSE INHIBIT
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents