Actual Value Correction Damping Factor / Actv_Corr D_Factor; Actual Value Correction Phase Currents / Actval_Corr I_Ph; Actual Value Correction Phase Voltages / Actval_Corr U_Ph; Motor Data Identification And Rotating Measurement - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
The load-dependent adaptation of the leakage inductance of the current actual value correction is defined using
p0391 ... p0393.
p1846[0...n]

Actual value correction damping factor / ActV_corr D_factor

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0.00
Description:
Sets the damping factor for the actual value correction.
The factor multiplies the T0/Tsig ratio in the feedback branch of the LR element.
r1848[0...5]

Actual value correction phase currents / ActVal_corr I_ph

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Displays phase correction currents as well as the drive converter phase currents
Index:
[0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
r1849[0...5]

Actual value correction phase voltages / ActVal_corr U_ph

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Displays the phase correction voltages and and the drive converter phase voltages
Index:
[0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
p1900
Motor data identification and rotating measurement / MotID and rot meas
VECTOR_G
Can be changed: C2(1), T
Data type: Integer16
P-Group: Motor identification
Not for motor type: -
Min
0
Description:
Sets the motor data identification and speed controller optimization.
p1900 = 0:
Function inhibited.
440
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.00
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
List Manual (LH2), 04/2014, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.00
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents