Bearing Version Selection / Bearing Vers Sel; Bearing Code Number Selection / Bearing Codeno Sel; Bearing Maximum Speed / Bearing N_Max - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0530[0...n]

Bearing version selection / Bearing vers sel

VECTOR_G
Can be changed: C2(1, 3)
Data type: Unsigned16
P-Group: Motor
Not for motor type: FEM
Min
0
Description:
Sets the bearing version.
Corresponding to the bearing version entered, its code number (p0531) is automatically set.
0 = No selection
1 = Manual entry
101 = STANDARD
102 = PERFORMANCE
103 = HIGH PERFORMANCE
104 = ADVANCED LIFETIME
Dependency:
Refer to: p0301, p0531, p0532, p1082
Notice:
For p0530 = 101, 102, 103, 104, the maximum bearing speed (p0532) is write protected. Write protection is
withdrawn with p0530 = 1.
If p0530 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3). The maximum speed of the bearing is factored into the limit for the maximum speed p1082.
Note:
For a motor with DRIVE-CLiQ, p0530 can only be set to 1.
p0531[0...n]

Bearing code number selection / Bearing codeNo sel

VECTOR_G
Can be changed: C2(3)
Data type: Unsigned16
P-Group: Motor
Not for motor type: FEM
Min
0
Description:
Display and setting the code number of the bearing.
When setting p0301 and p0530 the code number is automatically preassigned and is write protected. The information
in p0530 should be observed when removing write protection.
Dependency:
Refer to: p0301, p0530, p0532, p1082
Notice:
If p0531 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3). The maximum speed of the bearing is factored into the limit for the maximum speed p1082.
Note:
p0531 cannot be changed on a motor with DRIVE-CLiQ.
p0532[0...n]

Bearing maximum speed / Bearing n_max

VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: FEM
Min
0.0 [rpm]
Description:
Sets the maximum speed of the bearing.
The following applies when calculating the maximum speed (p1082):
- for p0324 = 0 or p0532 = 0, p0322 is used.
- for p0324 > 0 and p0532 > 0, the minimum value from the two parameters is used.
Dependency:
Refer to: p0301, p0322, p0324, p0530, p1082
212
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
104
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
210000.0 [rpm]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [rpm]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents