Friction Characteristic Record Ramp-Up/Ramp-Down Time; Friction Characteristic Record Warm-Up Time / Frict Rec T_Warm; Number Of Braking Modules Connected In Parallel; Bo: Braking Module Inhibit/Acknowledgement - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p3846[0...n]
Friction characteristic record ramp-up/ramp-down time / Frict rec t_RU/RD
VECTOR_G (n/M)
Can be changed: T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
0.000 [s]
Description:
Sets the ramp-up/ramp-down time of the ramp-up/ramp-down function generator to automatically record the friction
characteristic.
The drive is accelerated from standstill (setpoint = 0) up to the maximum speed/velocity (p1082) in this time.
Dependency:
Refer to: p3845
p3847[0...n]

Friction characteristic record warm-up time / Frict rec t_warm

VECTOR_G (n/M)
Can be changed: T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
0.000 [s]
Description:
Sets the warm-up time.
For an automatic trace (record) to start, the highest selected speed (p3829) is approached and this time is held. After
this, the measurement is started with the highest speed.
Dependency:
Refer to: p3829, p3845
p3860
Number of Braking Modules connected in parallel / BM qty par_cct
B_INF (Brk Mod ext)
Can be changed: C2(2)
Data type: Unsigned8
P-Group: Converter
Not for motor type: -
Min
1
Description:
Sets the number of Braking Modules connected in parallel in a DC link.
Note:
The parameter can only be written to if the infeed is in the commissioning mode (p0010 = 2).
r3861.0...7
BO: Braking Module inhibit/acknowledgement / BM inhib/ackn
B_INF (Brk Mod ext)
Can be changed: -
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
-
Description:
Signal to energize terminal X21.1 "inhibit/acknowledgement" on the Braking Module.
This binector output is used as signal source to interconnect to a digital output.
For "booksize" formats the digital output must be connected to terminal X21.1 and for "chassis" formats the digital
output must be connected to terminal X21.3 of the particular Braking Module.
Bit field:
Bit
00
01
02
03
04
05
06
07
588
Signal name
Inhibit/acknowledge Braking Module 1
Inhibit/acknowledge Braking Module 2
Inhibit/acknowledge Braking Module 3
Inhibit/acknowledge Braking Module 4
Inhibit/acknowledge Braking Module 5
Inhibit/acknowledge Braking Module 6
Inhibit/acknowledge Braking Module 7
Inhibit/acknowledge Braking Module 8
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
999999.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
3600.000 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
8
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
High
High
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 7010
Unit selection: -
Expert list: 1
Factory setting
10.000 [s]
Access level: 2
Func. diagram: 7010
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
Low
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents