Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note:
For distance-coded zero marks, this means the basic distance.
p0425[0...n]

Encoder rotary zero mark distance / Enc rot dist ZM

ENC, VECTOR_G
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the distance in pulses between two zero marks for a rotary encoder. This information is used for zero mark
monitoring.
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note:
For distance-coded zero marks, this means the basic distance.
p0426[0...n]

Encoder zero mark differential distance / Enc ZM Dif_dist

ENC, VECTOR_G
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
1
Description:
Sets the differential distance with distance-coded zero marks [signal periods].
The value corresponds to jump displacement of "zero mark with interference".
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
p0427[0...n]

Encoder SSI baud rate / Enc SSI baud rate

ENC, VECTOR_G
Can be changed: C2(4)
Data type: FloatingPoint32
P-Group: Encoder
Not for motor type: -
Min
0 [kHz]
Description:
Sets the baud rate for an SSI encoder.
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note:
SSI: Synchronous Serial Interface
p0428[0...n]

Encoder SSI monoflop time / Enc SSI t_monoflop

ENC, VECTOR_G
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
0 [µs]
Description:
Sets the minimum delay time between two data transfers of the absolute value for an SSI encoder.
160
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
16777215
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
65535 [kHz]
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
65535 [µs]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 4704, 8570
Unit selection: -
Expert list: 1
Factory setting
2048
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100 [kHz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
30 [µs]