p3238[0...n]

OFF delay n_act_motor model = n_act external / t_del n_a = n_ext

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: REL
Min
0.0 [s]
Description:
Sets the OFF delay for the signal "speed deviation model/external in tolerance" (BO: r2199.7).
The smoothed actual speed of the motor model r2169 is compared with the speed measured externally r1443
(threshold value p3236).
Dependency:
Refer to: p3236, p3237
p3320[0...n]

Fluid flow machine power point 1 / Fluid_mach P1

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 1 as a [%].
The characteristic comprises the following value pairs:
Power (P) / speed (n)
p3320 / p3321 --> point 1 (P1 / n1)
p3322 / p3323 --> point 2 (P2 / n2)
p3324 / p3325 --> point 3 (P3 / n3)
p3326 / p3327 --> point 4 (P4 / n4)
p3328 / p3329 --> point 5 (P5 / n5)
Dependency:
Refer to: r0041, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3321[0...n]

Fluid flow machine speed point 1 / Fluid_mach n1

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 1 as a [%].
The characteristic comprises the following value pairs:
Power (P) / speed (n)
p3320 / p3321 --> point 1 (P1 / n1)
p3322 / p3323 --> point 2 (P2 / n2)
p3324 / p3325 --> point 3 (P3 / n3)
p3326 / p3327 --> point 4 (P4 / n4)
p3328 / p3329 --> point 5 (P5 / n5)
Dependency:
Refer to: r0041, p3320, p3322, p3323, p3324, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
564
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.0 [s]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 8012
Unit selection: -
Expert list: 1
Factory setting
3.0 [s]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
25.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00