r0372[0...n]

Cable resistance / Mot R_cable

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
- [ohm]
Description:
Displays the total cable resistance between Motor Module and motor, as well as the internal converter resistance.
Dependency:
Refer to: r0238, p0352
r0373[0...n]

Motor rated stator resistance / Mot R_stator rated

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
- [ohm]
Description:
Displays the rated motor stator resistance at rated temperature (total of p0625 and p0627).
Dependency:
Refer to: p0627
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
r0374[0...n]
Motor rotor resistance cold / damping resistance d axis / Mot R_r cold/R_D d
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL
Min
- [ohm]
Description:
Displays the rotor/secondary section resistance of the motor for the ambient temperature p0625.
For separately-excited synchronous motors:
Displays the damping resistance in the rotor direction (d-axis).
Dependency:
Refer to: p0625
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
r0375[0...n]
Motor damping resistance q axis / Mot R_damp q
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PEM, REL
Min
- [ohm]
Description:
Displays the damping resistance of the separately-excited synchronous motor quadrature to the rotor direction (q
axis).
r0376[0...n]

Rated motor rotor resistance / Mot rated R_rotor

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
- [ohm]
Description:
Displays the nominal rotor / secondary section resistance of the motor at the rated temperature.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: MDS, p0130
Units group: 16_1
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: MDS, p0130
Units group: 16_1
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: MDS, p0130
Units group: 16_1
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: MDS, p0130
Units group: 16_1
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: MDS, p0130
Units group: 16_1
Scaling: -
Max
- [ohm]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]
Access level: 4
Func. diagram: -
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]
Access level: 4
Func. diagram: -
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]
Access level: 4
Func. diagram: -
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]
Access level: 4
Func. diagram: -
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]