Par_Circuit Circulating Current Control Operating Mode; Par_Circuit Circulating Current Control Proportional Gain; Par_Circuit Circulating Current Control Integral Time; Par_Circuit Circulating Current Control Limit / I_Circ Limit - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p7035[0...n]
Par_circuit circulating current control operating mode / I_cct_ctrl mode
VECTOR_G (Parallel) Can be changed: U, T
Data type: Integer16
P-Group: Modulation
Not for motor type: -
Min
0
Description:
Sets the operating mode of the circulating current control.
The circulating current control ensures symmetrical distribution of the total currents to the individual converters.
Value:
0:
1:
Dependency:
Circulating current control is not possible for separate, offset motor winding systems (p7003 = 2).
p7036[0...n]
Par_circuit circulating current control proportional gain / Circ_I Kp
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0.00000 [ohm]
Description:
Sets the proportional gain for the circulating current controller.
The parameter is pre-set to the cable resistance.
p7037[0...n]
Par_circuit circulating current control integral time / I_circ Tn
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
2.0
Description:
Sets the integral time of the circulating current controller.
The parameter is referred to the current controller sampling time (p0115[0]).
Dependency:
Refer to: p0115
p7038[0...n]

Par_circuit circulating current control limit / I_circ limit

VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
1 [%]
Description:
Sets the limit of the circulating current controller output values.
The parameter is, depending on the phase, referred to the valve lockout times (p1828, p1829, p1830).
704
Circulating current control de-activated
Circulating current control activated
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
200.00000 [ohm]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1000.0
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100 [%]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00000 [ohm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
4.0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50 [%]
SINAMICS G130/G150