p6999[0...4]

Recorder parameterization / Rec par

B_INF (Recorder),
Can be changed: U, T
VECTOR_G
Data type: Integer16
(Recorder)
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to parameterize the recorder.
The recorder supplies up to 64 internal variables (depending on the parameterization). The maximum recording time
is 2000 ms, the variables are acquired in the current controller sampling time – and a pretrigger can be set. The
values can then be acyclically written to the memory card. The development and system test departments have the
software necessary to decode the content.
Index:
[0] = Enable
[1] = Recording time
[2] = Pre-trigger time
[3] = Output message
[4] = Recording factor
Note:
Re index [0]:
Enables or disables the function.
p6999[0] = 0 inhibit the function.
p6999[0] = 1 enable the function. A POWER ON is required after the enable.
Re index [1]:
Sets the recording time, [ms]. The value is discretized with the current controller sampling time.
Re index [2]:
Sets the pretrigger time, [ms]. This time is included in the recording time and cannot be longer than the recording
time p6999[1]. The value is discretized with the current controller sampling time.
Re index [3]:
Enables or disables the output of message A49998 when the trigger event is triggered.
Re index [4]:
p6999[4] = n, n = 0 ...4
Recording with the factor, which extends the record time p6999[1] and the pre-trigger time p6999[2] 2^n times, and
reduces the number of signals 2^n times.
Example:
p6999[1] = 2000, p6999[2] = 1000, p6999[4] = 4
--> recording time: 2000 ms * 2^4 = 32 s, pre-trigger time:1000 ms * 2^4 = 16 s, number of signals 128/16 = 8.
When setting p6999[4] to 0, the results are as follows:
--> recording time: 2000 ms , pre-trigger time:1000 ms, number signals 128. The maximum number of signals
depends on the drive object.
r7000

CO: Par_circuit No. of active power units / Qty active PU

B_INF (Parallel),
Can be changed: -
VECTOR_G (Parallel)
Data type: Unsigned16
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Displays the active power units for a parallel circuit configuration.
Dependency:
Refer to: p7001
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2000
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: 8144
Unit selection: -
Expert list: 1
Factory setting
[0] 1
[1] 1000
[2] 900
[3] 0
[4] 0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
699