2 Parameters
2.2 List of parameters
r8960[0...2]

PN subslot controller assignment / PN subslot assign

B_INF, CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned8
CU_G150_DP,
P-Group: -
CU_G150_PN, ENC,
Not for motor type: -
TB30, TM150, TM31,
VECTOR_G
Min
0
Description:
Displays the controller assignment of a PROFINET subslot on the actual drive object.
Index:
[0] = Subslot 2 PROFIsafe
[1] = Subslot 3 PZD telegram
[2] = Subslot 4 PZD supplementary data
Dependency:
Refer to: r8961, r8962
Note:
Example:
If the parameter contains the value 2 in index [1], then this means that subslot 3 is assigned to controller 2.
r8961[0...3]

PN IP Address Remote Controller 1 / IP Addr Rem Ctrl1

CU_G130_PN,
Can be changed: -
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0
Description:
Displays the IP address of the first PROFINET controller connected with the device via PN onboard.
r8962[0...3]

PN IP Address Remote Controller 2 / IP Addr Rem Ctrl2

CU_G130_PN,
Can be changed: -
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0
Description:
Displays the IP address of the second PROFINET controller connected with the device via PN onboard.
p8969

PROFIsafe wait for clock synchronization / PS wait sync

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Setting for the behavior of a PROFIsafe communication connection depending on another isochronous
communication connection.
Value:
0:
1:
Recommend.:
A value of 1 is recommended, if problems are encountered with the PROFIsafe connection when synchronizing.
Note:
If value = 1:
A PROFIsafe connection is only accepted if an isochronous connection exists.
Relevant, if PROFIsafe and isochronous operation are configured via various communication connections (e.g.
PROFINET Shared Device).
832
No
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
8
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150