1.9

File Transfer Function

The file transfer function transfers logging files or report files to an FTP server or a file server that has a shared folder.
There are three file transfer functions as follows:
• Transfer Function: Transfers logging files to the specified file server at the file switching timing.
• Resend function: Resends logging files to the specified file server when a file transfer is failed.
• Transfer completion notification function: Notifies the transfer completion by transferring a transfer completion file to the
specified file server.
Transfer function
This function transfers the latest saved file to the file server when the file is switched.
Accumulating file
To save a file on the file server having same saved file name, the transfer function will overwrite the file on the server to the
saved file.
For details on the folder configuration after a file transfer, refer to the following:
MELSEC iQ-R High Speed Data Logger Module User's Manual (Startup)
Precautions
The file on the transfer destination may get corrupted if the CPU module is turned OFF or reset when the file is being
transferred.
If any problem arises, turn OFF the power or reset the CPU module after stopping the file access.
1 FUNCTION
94
1.9 File Transfer Function
(New) 'Saved files'
File switching
Transfer
FileName_01
FileName_02
FileName_01
File server (FTP server, shared folder)
Ethernet
High speed data
SD memory card
logger module