Mitsubishi Electric MELSEC iQ-R Series User Manual page 347

High speed data logger module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Trigger logging
■High speed sampling
• Measurement conditions
Item
Access target CPU
Data logging setting
SD memory card
Measuring method
• Measurement results
Use the measurement results as a reference for processing time.
Processing time changes according to the settings and external factors such as access from GX LogViewer. (Page 344
Processing Time)
Item
Sampling speed (milliseconds)
*1
Trigger logging interval
(seconds)
*2*3
File save time
(seconds)
*1 The maximum time before/after the trigger where data can be retained and output to a file when a trigger occurs.
*2 The time required to output 100 lines (records) of data before/after the trigger.
*3 If the file switching and folder switching have occurred, the file save time will be longer by one second.
CPU module
Network
Sequence scan time
Logging type
Sampling
Data
Unicode text output
Binary output
CSV output
File
Data logging amount
Sampling speed
File save time
Number of device points
16
0.5
32.8
Unicode text file
0.7
Binary file
0.5
CSV file
0.6
Description
R04CPU
Own station (single CPU system configuration)
The sequence scan time that can be sampled is displayed in the
measurement result.
Trigger logging
Data logging 01 to 32: High speed sampling (each scan)
D devices
Data type: Word [signed] decimal format (digits: 0)
• A date column is output.
• An index column is output.
• Date information is output.
• An index is output.
• A date column is output.
• An index column is output.
File switching timing: 1000 lines
Number of saved files: 256
Number of device points 16 to 1024: Data logging 01
Number of device points 4096: Data logging 01 to 04
Number of device points 8192: Data logging 01 to 08
Number of device points 16384: Data logging 01 to 16
Number of device points 32768: Data logging 01 to 32
NZ1MEM-16GBSD
Data is sampled for each scan and the sequence scan time which can perform
trigger logging is measured.
The time taken from when data corresponding to the number of lines before
and after trigger has been sampled up to when saving it to a file is completed
is measured.
64
256
1024
4096
0.6
0.9
2
6
29.1
15.7
9.8
7.4
0.8
1.2
3
11
0.5
0.6
1.6
8
0.7
0.7
2.5
10
8192
16384
32768
10
18
32
6.1
5.5
4.9
25
50
220
21
40
120
23
44
150
APPX
Appendix 7 Processing Time
A
345

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-rd81dl96Melsec iq-sw1dnn-rdlutl

Table of Contents