Save function

This function saves event logging target data in the event logging file.
Event logging file save format
Event logging files can be saved in the following three types of format on a high speed data logger module.
• Unicode text file format (extension: .TXT)
• Binary file format (extension: .BIN)
• CSV file format (extension: .CSV)
For details on each file format, refer to the following:
Page 364 Event Logging File Format
■Unicode text file format
Unicode text file format is a file format that can be opened by a general application such as Excel and notepad.
It can also be viewed with GX LogViewer.
■Binary file format
High-speed file access is possible with this format because it is smaller in size than the CSV file format.
It can be viewed with GX LogViewer.
■CSV file format
CSV file format is a file format that can be opened by a general application such as Excel and notepad.
It can also be viewed with GX LogViewer.
Saving event logging files
The high speed data logger module temporarily saves events to the 'accumulating file' on the SD memory card that is inserted
in the high speed data logger module.
Since the size of an accumulating file becomes larger with time, a file is switched with the specified conditions.
The specified information such as date and time can be added to the file name.
The method for file switching and saving files is the same as that of the data logging file. For more details, refer to the
following:
However, "Trigger logging unit" cannot be specified for the file switching timing.
Page 50 Saving data logging files
■Event logging file save location
Event logging files are saved in the SD memory card.
For the SD memory card directory structure, refer to the following:
MELSEC iQ-R High Speed Data Logger Module User's Manual (Startup)
Edit function of the saved folder
A setting type folder or a subfolder to which information can be added, can be specified for a saved folder to store saved files.
The edit function of the saved folder is same as the data logging file. For more details, refer to the following:
Page 54 Edit Function of the saved folder
Transferring event logging files
Event logging files can be automatically transferred to an FTP server or shared folder, or mail server.
There are two methods for transferring event logging files.
• Transferring to the FTP server and shared folder (Page 94 File Transfer Function, Page 136 File transfer setting)
• Sending e-mail (Page 97 E-mail Function, Page 139 E-mail setting)
When transferring files to the FTP server and shared folder, the event logging file destination defers depending on the saved
folder specifications.
For details of each folder structure at the time of file transfer, refer to the following:
MELSEC iQ-R High Speed Data Logger Module User's Manual (Startup)