Error code
Error name
18B4H to 18BDH
High speed sampling error
18BEH
High speed sampling error
18BFH to 18C0H
High speed sampling error
18C1H to 18C2H
High speed sampling
unsupported CPU error
18C3H to 18CCH
High speed sampling error
18CDH
High speed sampling error
18CEH to 18D0H
High speed sampling error
18D1H to 18D2H
High speed sampling
unsupported CPU error
18D3H to 18DCH
High speed sampling error
18DDH
High speed sampling error
18DEH to 18E0H
High speed sampling error
18E1H to 18E2H
High speed sampling
unsupported CPU error
18E3H to 18E9H
High speed sampling error
18EAH
High speed sampling error
18EBH
High speed sampling error
18ECH
High speed sampling error
Error description
Failed to execute the high speed sampling.
• Module operation is executed by more than one
location at the same time.
• Failed to execute the high speed sampling.
Failed to execute the high speed sampling.
The control CPU does not support high speed
sampling.
Failed to execute the high speed sampling.
• Module operation is executed by more than one
location at the same time.
• Failed to execute the high speed sampling.
Failed to execute the high speed sampling.
The control CPU does not support high speed
sampling.
Failed to execute the high speed sampling.
• Module operation is executed by more than one
location at the same time.
• Failed to execute the high speed sampling.
Failed to execute the high speed sampling.
The control CPU does not support high speed
sampling.
Failed to execute the high speed sampling.
Total device points of each module setting
performing 'high speed sampling (synchronizes to
the sequence function)' from same control CPU
exceeds the maximum points.
(Access points is calculated rounding up at 8192
points unit.)
• Total module number performing 'high speed
sampling (synchronizes to the sequence
function)' from same control CPU exceeds
maximum module number.
• Module operation is executed by more than one
location at the same time.
• Failed to start high speed sampling.
• Module operation is executed by more than one
location at the same time.
Corrective action
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Execute update settings again.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Replace it with a CPU that supports high speed
sampling.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Execute update settings again.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Replace it with a CPU that supports high speed
sampling.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Execute update settings again.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Replace it with a CPU that supports high speed
sampling.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Check the number of high speed sampling
device points.
• Change the sampling method to general
sampling.
• Configure the setting of control CPU so that
total device points of each module setting using
'high speed sampling (synchronizes to the
sequence function)' dose not exceed the
maximum points.
• Change the sampling method to general
sampling.
• Configure the system so that module number
using "high speed sampling (synchronizes to
the sequence function)" dose not exceed the
maximum number.
• Execute update settings again.
• Restore the device points to points before
updating setting.
• Cycle the power of the system where the high
speed data logger module is mounted or reset
the CPU module.
• Check the number of high speed sampling
device points.
• Change the sampling method to general
sampling.
• Execute update settings again.