Mitsubishi Electric MELSEC iQ-R Series User Manual page 184

High speed data logger module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Event setting (compound condition)
Window
Displayed items
Item
Comparison
AND combine
OR combine
Number of times
When a terminal condition holds true
When a specified number of times is
exceeded
Conditions for the occurrence of an
event
Order
Abnormal pattern is detected
Normal pattern is detected
Detect timeout
Condition list
Type
Contents of settings
Start condition
Terminal condition
Count condition
Start condition
1st/2nd/3rd condition
Monitoring timeout [Second]
[Edit] button
[Delete] button
*1 Displayed in the case of "Number of times."
*2 Displayed in the case of "Order."
*3 When selecting "Number of times" or "Order," the conditions which can be set are "Comparison" and "Value change."
*4 When selecting "Order", the monitoring timeout can be specified.
2 HIGH SPEED DATA LOGGER MODULE CONFIGURATION TOOL
182
2.6 Event Logging Setting
Description
Select this to make an event occur by comparing monitoring data and the condition is satisfied.
Select this to make an event occur when all the specified conditions in the condition list are
satisfied.
Select this to make an event occur when any of the specified conditions in the condition list is
satisfied.
Select this to make an event occur by monitoring the number of times the condition is satisfied.
Select this to check the number of counts when the termination condition is satisfied, and make
an event occur when the specified condition is satisfied.
Select this to make an event occurs immediately when the number of counts exceeds the
specified count.
Specify the conditions (comparison operator and number of times) to compare the number of
times the count condition is satisfied (number of counts).
Select this to make an event occur by monitoring the order of the condition satisfaction.
Select this to make an event occur when the condition is satisfied with an order different from
the one specified in the condition list.
Select this to make an event occur when the condition is satisfied with the order specified in the
condition list.
Select this to make an event occurs when any of the conditions are not satisfied within the
monitoring timeout.
Displays the condition type.
Displays the overview of the condition.
*1
Displays the condition to start counting for the number of counts.
*1
Displays the condition to stop counting for the number of counts.
*1
Displays the condition to increment the number of counts.
*2
Displays the condition to start monitoring the order that the condition is satisfied.
*2
Displays the conditions to monitor in order.
*2
Displays the timeout time when monitoring the conditions in each order.
Displays the setting screen to edit the selected condition.
The settings are same as mentioned in the following section.
Comparison: Page 181 Event setting (single condition)
Number of times, Order: Page 158 Trigger condition setting
Deletes the selected condition.
*3*4