Module operating status (X5)
● This signal turns ON when the data logging function, event logging function, and report function are operating.
● This signal turns OFF when the data logging function, event logging function, and report function are stopped.
It will be in stop state in the following situations.
• When a module operation is stopped in Configuration Tool
• When the settings are not written to the high speed data logger module
• When an module stop error occurs
• When file access is stopped (X2 is ON)
The data logging function, event logging function, and report function will start operating again according to the following
procedure.
• When a module operation is stopped in Configuration Tool
1.
Restart the module operation in Configuration Tool. (Page 216 Module diagnostics)
• When the settings are not written to the high speed data logger module
1.
Write settings to the high speed data logger module in Configuration Tool. (Page 214 Write)
2.
Update the settings. (Page 216 Module diagnostics)
• When a module stop error occurs
1.
Clear the error in Configuration Tool or 'error clear request' (Y10). (Page 216 Module diagnostics)
2.
Update the settings in Configuration Tool. (Page 216 Module diagnostics)
• When file access is stopped (X2 is ON)
1.
Turn ON 'Clear file access stop request' (Y3). (File access starts (X2 turns OFF).
2.
Restart the module operation or update the settings in Configuration Tool. (Page 216 Module diagnostics)
INFO LED status (X7)
This signal turns ON when INFO LED turns ON.
For the factors that the INFO LED is turned ON, refer to the following:
Page 216 Module diagnostics, Page 310 Module status area (Un\G0 to 20)
This signal turns OFF by turning the 'clear INFO LED request' (Y7) ON to turn the INFO LED OFF.
This signal turns OFF by updating the settings.
Setting renew status (X8)
This signal turns ON when settings are updated by turning ON 'Setting renew request' (Y8).
'Setting renew status' (X8) turns OFF when 'Setting renew request' (Y8) is turned OFF after 'Setting renew status' (X8) turns
ON.
Time synchronization timing (XB)
This signal turns ON when a time inquiry is successful for the time synchronization request by turning ON 'Time
synchronization request' (YB).
If the 'time synchronization timing' (XB) turns ON, then 'time synchronization request' (YB) turns OFF, the 'time
synchronization timing' (XB) turns OFF.
APPX
Appendix 2 Input/Output Signals
A
295