Error code
Error name
1FF7H to 1FF8H
Directory creation error
2121H
SD memory card error
2440H
Module major error
2450H
Module major error
24C0H to 24C1H
System bus error
24C2H
System bus error
24C3H
System bus error
24C4H to 24C5H
System bus error
24C6H
System bus error
24C8H
System bus error
Error description
Failed to create the directory.
An error has been detected in the SD memory
card.
• In the multiple CPU system, the control CPU
setting in the system parameters is different
from that of other numbered CPU modules.
• An error has been detected in the I/O module or
intelligent function module during the initial
processing.
• A major error has been detected from the I/O
module or intelligent function module.
An error has been detected on the system bus.
An error has been detected on the system bus.
An error has been detected on the system bus.
An error has been detected on the system bus.
An error has been detected on the system bus.
An error has been detected on the system bus.
Corrective action
• Check if the file is being deleted.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Format or reinsert the SD memory card. If the
same error is displayed again, a hardware
failure may occur in the SD memory card.
Replace the SD memory card.
• When the write protect switch of the SD
memory card is locked, unlock the switch and
insert the card.
• Review the system parameters of the second or
higher numbered CPU modules and match
them with those of the smallest numbered CPU
module.
• A hardware failure may occur in the module.
Please consult your local Mitsubishi
representative.
• Check the connection status of the extension
cable.
• Check that the I/O module or intelligent function
module is mounted correctly.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the module. Please consult
your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the CPU module, I/O
module, intelligent function module, base unit,
or extension cable. Please consult your local
Mitsubishi representative.
• Check the connection status of the extension
cable.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the CPU module, I/O
module, intelligent function module, base unit,
or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the CPU module, I/O
module, intelligent function module, base unit,
or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the CPU module, I/O
module, intelligent function module, base unit,
or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the CPU module or
extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the I/O module, intelligent
function module, or extension cable. Please
consult your local Mitsubishi representative.