■Normally completed file transfer count (Un\G6004)
The total number of times the high speed data logger module transfers an file to the file server is saved.
■Abnormally completed file transfer count (Un\G6005)
The total number of times of communication error which are returned when the high speed data logger module requests the
file server to transfer an file is stored.
■Transfer result 1 to 16 (Un\G6006 to 6037)
The total number of transfer results is stored for each transfer destination setting number.
Transfer result area is comprised of 16 pieces of transfer results with the same data configuration.
Un\G6006 to 6007
Un\G6008 to 6009
Un\G6036 to 6037
● Normally completed file transfer count
The number of times transfer is normally completed in the transfer destination setting is stored.
● Abnormally completed file transfer count
The number of times transfer is abnormally completed in the transfer destination setting is stored.
■Error log write count (Un\G6038)
The total number of times an error log is registered in the error log area is stored.
The error code is stored when 'file transfer error' (X18) is ON.
■Error log write pointer (Un\G6039)
The error log No. where the latest error log is registered is stored. (For example, when the pointer value is '16', it indicates that
the latest error log is registered in the area of the error log '16'.)
0: No error (No registration of error log)
1 or more: The error log No. where the latest error log is registered
When 17 or more error logs occur, the error logs are registered again from error log 1 area.
■Error log 1 to 16 (Un\G6040 to 6519)
The error log when file transfer is abnormally completed is stored.
Error log area is comprised of 16 error logs with the same data configuration.
Un\G6040 to 6069
Un\G6070 to 6099
Un\G6490 to 6519
● Error code
The error code is stored.
● Transfer destination setting number
The transfer destination setting No. when communication error occurs is stored.
Transfer destination settings are set in the file transfer destination settings.
● File name
The file name is stored in ASCII code.
● Date
The time when the file was transferred is stored in BCD code.
APPX
332
Appendix 3 Buffer Memory
Transmission log 1
Transmission log 2
Transmission log 16
Error log 1
+0
Error log 2
+1
+2
+25
+26
+27
Error log 16
+28
+29
b15
Normally completed file count
+0
+1
Abnormally completed file count
b15
Transfer destination setting number
Month (01H to 12H)
Hour (00H to 23H)
Second (00H to 59H)
Year (00H to 99H) first 2 digits
b8
b7
b8
b7
Error code
File name
Year (00H to 99H) last 2 digits
Day (01H to 31H)
Minute (00H to 59H)
Day of the week (0H to 6H)
b0
b0
Date