Ekip Touch - Default; Ekip Touch Default Parameters - ABB SACE Emax 2 Series Operating Instructions Manual

Low voltage air circuit-breaker
Table of Contents

Advertisement

Ekip Touch - Default

1 - Ekip TOUCH default parameters

Foreword Given the number of parameters available with Ekip Touch, each chapter describing their characteristics
Protections All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
Parameters Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
147 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
also includes their default value settings.
The configurations of the main parameters are given below.
exception of the protections listed below:
Protection
L (excluding Ekip M Touch)
L (only Ekip M Touch)
L
(1)
I
I
Harmonic distortion
Rc
(1)
Rc
(2)
protection always active; a model L Disable rating Plug must be used to disable it
(1)
protection available and active if model Rc Rating Plus is present
(1)(2)
following configurations:
Parameters
Frequency
Configuration
Neutral
Rated voltage
Power flow
Phase Sequence
Local bus
Mode
Language
Bluetooth Low Energy
Password
Home page
LED Alive
View
Maintenance
Test Bus
Modbus RTU par
Profibus
DeviceNet
TM
Modbus TCP/IP
Configuration
I1= 1 In; t1= 12 s; curve= t= k/I
I1I1= 1 In; t1= 48 s; curve= t= k/I
90% I1
I1= 1 In; t1= 22 s (Class= 10E); Thermal Memory=
On; Prealarm: 90 % I1I1= 0,4 In; t1= 45 s (Class=
20E); Thermal Memory= On; Prealarm: 90 % I1
I1= 1 In; t1= 144 s; curve= t= k/I
I1
I3= 5.5 In (all except Ekip M Touch) / 6 In (Ekip M
Touch); startup= OFF
I3= 4 In; startup= OFF
On
Idn= 3 A; Tdn= 0,06 s
Idn= 3 A; Tdn= 0,06 s
Configuration
50 Hz (IEC) / 60 Hz (UL)
3P (3P circuit-breaker) / 4P (4P circuit-breaker)
Off (3P circuit-breaker) / 50% (4P
circuit-breaker)
400 V
Bottom → Top
1-2-3
Off
Local
English
Off
00001
Histograms
Disabled
Horizontal
On
On
Address: 247; baudrate: 19.2 kbit/s
Address: 125
MAC ID: 63; baudrate: 125 kbit/s
Static IP: 0.0.0.0
1 - Ekip TOUCH default parameters
ABB | SACE Emax 2
; prealarm: 90%
2
; prealarm:
2
; prealarm: 90%
2
Ekip Touch - Default