ABB SACE Emax 2 Series Operating Instructions Manual page 63

Low voltage air circuit-breaker
Table of Contents

Advertisement

G Protection
t
I4
t4
60 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Function
Ekip Touch calculates the vector sum of the phase currents (L1, L2, L3, Ne) and obtains the internal earth
fault current (Ig): if current Ig exceeds threshold I4, the protection trips and, after a time established by
G
the value read and by the parameter settings, transmits the TRIP command.
To check and simulate the trip times in relation to all the parameters, please consult:
• the summary table of the protections with the calculation formulas (page 95)
• the graph with trip curve (page 103)
Parameters
I
Parameter
Description
Activates/deactivates the protection and its availability in the
Enable
parameters menu.
Activates/deactivates transmission of the open command. If
Trip Enable
disabled, the alarm and exceedance of protection time are only
managed as information.
Establishes curve dynamics and the threshold or trip time
calculation:
Curve
Establishes the value that activates the protection and
contributes towards calculating the trip time.
Threshold I4
The value is given as both absolute value (A) and relative value (In)
and can be set within the range: 0.1 In to 1 In, in 0.001 In steps
It is the trip time or contributes towards timing calculation,
depending on the type of curve selected.
The value is given in seconds and can be set within the range: 0.1
Time t4
s to 1 s, in 0.05 s steps
Warns that the measured current is near to the protection
activation threshold.
The value is given in percentage of threshold I1 and can be set
Prealarm I4
within the range 50% I4 to 90% I4, in 1% steps.
The prealarm condition deactivates in two cases:
Activates/deactivates the function and selectivity time availability
on the display (page 83)
ZoneSelectivity
This is the trip time of the protection with the zone selectivity
function activated and selectivity input not present (page 83)
Selectivity time
The value is given in seconds and can be set within the range:
0.04 s to 0.2 s, in 0.01 s steps
Activates/deactivates the function and availability of the
StartUp enable
associated parameters on the display (page 86)
Protection threshold valid during Startup time, in the conditions
StartUp
in which the function is activated (page 86)
Threshold
The value is given as both absolute value (A) and relative value (In)
and can be set within the range: 0.2 In to 1 In, in 0.02 In steps
This is the time for which the StartUp threshold remains
activated, as calculated from the moment the activation
StartUp Time
Threshold is exceeded (page 86)
The value is given in seconds and can be set within the range: 0.1
s to 30 s, in 0.01 s steps
• t = k: fixed time trip
• t = k/I
: inverse time-delay dynamic trip
2
NOTE: in the presence of curve: t = k, t4 can also be
configured as: instantaneous; in this mode, the trip time is
comparable to that given for I protection (page 95)
• current lower than prealarm threshold I4
• current higher than threshold I4
NOTE: the function is only available with curve t = k
ABB | SACE Emax 2
Default
OFF
ON
t = k
0,2 In
0.1 s
90 % I4
OFF
0,04 s
OFF
0,2 In
0.1 s
Continued on the next page
Ekip Touch - Protections