ABB SACE Emax 2 Series Operating Instructions Manual page 87

Low voltage air circuit-breaker
Table of Contents

Advertisement

D zone selectivity Protection Foreword
84 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Configuration
To correctly configure the selectivity network of one or more protections:
1. Connect zone selectivity outputs of the same type (example: Szo) of devices belonging to the same
zone, to the zone selectivity input of the device immediately upstream (example: Szi).
2. Connect all the Szc of devices in the same network together.
3. Time t2 must be configured at t2 sel + 50 ms or more, with the exclusion of the device further along
its network.
Logic table
The table includes all cases in which, with zone selectivity enabled in the device, an alarm condition occurs
or a zone selectivity signal is received from another device.
NOTES:
• the table gives the S protection cases, but is also valid for the other protections: G, S2, I, 2I,
MCR, Gext and MDGF, each with its respective connections
• if the selectivities of protections that share the same connections are active at the same
time (example: S, S2, I, 2I and MCR), the inputs/outputs are managed with OR logic
Condition
Szi
Szo
If < I2
0
0
If < I2
1
1
If > I2
0
1
If > I2
1
1
the trip time of protection I is that of protection
(1)
for I protection tripping time is 100ms
(2)
This function, which can be activated for D protection (if available and enabled), enables devices
belonging to the same installation (including Ekip Touch) to be connected together so as to handle the
trip commands in a better way in the case of D protection.
It is especially useful in ring and grid type systems where, besides the zone, it is essential to also define
the direction of the power flow that supplies the fault.
The function allows the devices to be coordinated so that, if a fault occurs:
• the device nearest to the fault trips
• The other devices are blocked for a programmable time
NOTES:
• connection can be made between ABB devices that have the zone selectivity function
• disable the zone selectivities of protections S, S2, I, 2I, MCR, G, Gext and MDGF to correctly
use the selectivity D function
Characteristics
Ekip Touch has five selectivity connections, located on the upper terminal box of the CB:
Name
Type
Szi
Input
Szo
Output
Gzi
Input
Gzo
Output
Szc
Common
Tripping
Remarks
time
No TRIP
TRIP Il device not in alarm status
The device is not in the alarm status, but sends the
No TRIP
selecitivity signal received from the device upstream
The device is in the alarm status and is the first to
t2 sel
(1)
detect the fault: trips within time t2 sel
The device is in the alarm status but is not the first
t2
(2)
to detect the fault: trips within time t2
Description
Forward direction selectivity input
Forward direction selectivity output
Backward direction selectivity input
Backward direction selectivity output
Common connection of selectivity
network
ABB | SACE Emax 2
(1)
(2)
Denomintion for D
DFin
DFout
Dbin
Dbout
SZc
Continued on the next page
Ekip Touch - Protections
9 - Additional protections and functions