Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
Remote configurations The operating configuration can be changed from slave to master via the service connector (via Ekip
Remote information Certain additional information concerning the version and status of the module is available via the service
215 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
is available in the Settings menu (page 133).
Two areas are activated if Ekip Touch detects the module correctly:
• information area in the About-Modules menu, containing the software version and serial number
of the module
• specific configuration area in the Settings-Modules menu, where the following communication
parameters can be configured
Parameter
Description
Module address; 1 to 247 range available
Serial address
IMPORTANT: devices connected to the same network must
have different addresses
Data transmission speed; 3 options are available: 9600 bit/s,
Baudrate
19200 bit/s, 38400 bit/s
Defines the stop and parity bit; 4 options are available:
• 8,E,1 = 8 data bits, 1 EVEN parity bit, 1 STOP bit
Physical
• 8,O,1 = 8 data bits, 1 ODD parity bit, 1 STOP bit
protocol
• 8,N,2 = 8 data bits, no parity bit, 2 STOP bits
• 8,N,1 = 8 data bits, no parity bit, 1 STOP bit
247 default of the Ekip Com Modbus RTU module; 246 default of the Ekip Com Modbus RTU
(1)
Redundant module
Connect) or via system bus communication so as to integrate the module into an interactive data
exchange network (see description of Ekip Com Hub, page 240).
IMPORTANT:
• In the Master configuration, the module does not allow data exchange as in the normal
Slave function
• the presence of several masters in the same network can cause faulty operation
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).
ABB | SACE Emax 2
Default
247 / 246
(1)
19200 bit/s
8,E,1
External electronic accessories
2 - Ekip Com Modbus RTU