ABB SACE Emax 2 Series Operating Instructions Manual page 204

Low voltage air circuit-breaker
Table of Contents

Advertisement

S51: trip unit tripping
signalling contact
201 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
The S51 contact signals the opening of the circuit-breaker due to tripping of the Ekip protection trip unit.
It is available in two different types:
• standard contact
• contact for digital signals
NOTE: The standard S51 contact is always included in automatic circuit-breakers, and is
associated with the TU Reset mechanical signalling.
95
96
98
S51
S51 for E1.2
S51 for E2.2 - E4.2 - E6.2
The following table provides information on the electrical characteristics:
Characteristics
24V
125V
DC
Breaking
250V
capacity
AC
125V - 250V
Minimum load
S51: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet
kit sheet 1SDH001000r0605.
95
96
98
S5 1
Standard
-
0.3A @ 0ms
0.15A @ 10ms
0.3A @ 0ms
0.15A @ 10ms
1,5A cosφ 0,3
3A cosφ 0,7
5A cosφ 1
100mA @ 24V
1SDH000999r0605
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
1mA @ 5V
and for E2.2-E4.2-E6.2 in the
Electrical accessories
2 - Electrical signalling accessories