ABB SACE Emax 2 Series Operating Instructions Manual page 241

Low voltage air circuit-breaker
Table of Contents

Advertisement

Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
Information in menu The following information will be available in the About - Modules menu if Ekip Touch has detected the
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
238 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
is available in the Settings menu (page 49).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings - Modules menu:
Parameter
Static IP address ON
Static address IP address
Static Network Mask
Static Gateway address
module correctly:
Information
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the
time of connection to the network in the case of configuration with a
IP address
dynamic IP, or can be set via the menu in the event of a static IP
Subnet mask; identifies the method for recognizing the subnet to which
Network Mask
the modules belong and enables modules to be searched for within a
defined set of recipients.
IP address of the node to which the module is connected, in the presence
Gateway address
of several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
MAC address
equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
communication:
Parameter
Description
Parameter for changing the configuration of the module
from Server Only to Client and Server and for integrating it
into an interactive data exchange network (see Ekip Com
Client/Server
Hub on page 240).
Allows the IEEE 1588 protocol for distribution of the clock
Enable IEEE 1558
and synchronization signal to be enabled
Enables the module to be set up as a master in the the
IEEE 1558 Master
network segment to which it belongs (synchronization
clock).
IEEE 1558 Delay
Allows the data exchange mode between module and
mechanism
master, either Peer-to-Peer or End-to-End, to be selected.
Allows the SNTP protocol for distribution of the clock and
Enable client SNTP
synchronization signal to be enabled
Allows the network server that supplies the SNTP to be
ANTP Server address
set.
Time zone
Defines the time zone to be used for synchronism
Used to select whether daylight saving time is
Daylight Saving Time
present (ON) or not (OFF) in the country to which the
synchronization time refers
Description
Defines whether the module has the dynamic (Off) or
static (On) IP address.
Se = On all the associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
When there are several subnets, enables the IP address of
the node to which the module is connected to be selected
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
IMPORTANT: if Client/Server, the module allows
data exchange like a normal Server function
ABB | SACE Emax 2
OFF
0.0.0.0
0.0.0.0
0.0.0.0
Default
Server only
OFF
.
(1)
OFF
End-to-End
Off
(1)
0.0.0.0
+00:00
OFF
Continued on the next page
External electronic accessories
9 - Ekip Link
Default