Interface the module has three signaling leds:
Configurations via menu The specific configuration area will activate in the Advanced - Synchrocheck menu if the Ekip Synchrocheck
249 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Figure 139
LED
Description
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present, flashing not synchronized with
the Power led of Ekip Touch (two fast flashes per second): module on and
communication with Trip unit absent
Indicate the status of the contacts of each output:
• off: contact open
• on: contact closed
O SC
NOTE: The LED displays the state of the output: it can indicate
synchronization OK or KO, depending on the contact rest configuration
(normally open or closed)
module is detected correctly by Ekip Touch.
Parameter
Description
Activates/deactivates the protection and its availability in the
Enable
parameters menu
Dead bar option
On = busbar activated; Off = dead busbar present
Maximum external voltage (with dead busbar and configuration:
Udead Threshold
Normal
(1)(2)
The value is given as both absolute value (V) and relative value (Un)
and can be set within the range: 0.02 Un to 2 Un, in 0.001 Un steps
Minimum voltage for starting monitoring of external voltage (with
busbar activated) or internal voltage (with dead busbar and Normal
Ulive Threshold
configuration)
(2)(3)
The value is given as both absolute value (V) and relative value (Un)
and can be set within the range: 0.5 Un to 1.1 Un, in 0.001 Un steps
Minimum time within which the Ulive Threshold condition must be
obtained in order to activate voltage monitoring
Stability Time
The value is given in seconds and can be set within the range: 100
ms to 30 s, in 1 ms steps
Maximum difference between internal and external voltage (first
synchronism condition)
Delta Voltage
The value is given as both absolute value (V) and relative value (Un)
and can be set within the range: 0.02 Un to 0.12 Un, in 0.001 Un steps
Maximum difference between internal and external frequency
(second synchronism condition)
Delta frequency
(4)
The value is given in Hertz and can be set within the range: 0.1 Hz to
1 Hz in 0.1 Hz steps
Maximum difference between internal and external phase (third
synchronism condition)
Delta phase
(4)
The value is given in degrees and can be set within the range: 5° to
50° in 5° steps
is the first synchronism condition)
(2)
ABB | SACE Emax 2
Default
Off
Off
0.2 Un
0.5 Un
1 s
0.12 Un
0.1 Hz
50 °
Continued on the next page
External electronic accessories
12 - Ekip Synchrocheck