5 - Network Analyzer

Presentation The Network Analyzer function allows you to set voltage and current controls over a long period, in order
Parameters The configuration parameters of the counters are available in the Settings - Network Analyzer menu (page
123 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
to analyze your system.
To this purpose, voltages and currents are monitored, so as to find:
• voltage sequences (Over, Under, Pos and neg)
• unbalance between voltages (Unbalance)
• short voltage drops (Interruption) and slow sags (Sag)
• short voltage increases (Spikes) and slow swells (Swell)
• harmonic distortion of voltages and currents (THD)
Each monitoring is associated with control parameters set by the user and updated each time the set
control conditions occur.
49).
The Monitor time parameter, which defines the length of each monitoring session, can also be set in the
Settings menu.
NOTE: the parameter is the one used for measuring the maximum currents and voltages
Main Menu
Parameter
Description
Activates/deactivates the function and its availability in the
Enable
parameters menu
I Harmonic
Activates harmonic analysis of the currents
Analysis
V Harmonic
Activates harmonic analysis of the voltages
Analysis
Control threshold of the Under V Th counter
V Threshold
The value is given as a percentage of rated voltage Un and can be
Low
set within the range: 75% to 95%, in 5% steps.
Control threshold of the Over V Th counter
V Threshold
The value is given as a percentage of rated voltage Un and can be
High
set within the range: 105, 110, 115 % Un
Alarm threshold for the Unbalance counter.
The value is given as a percentage of rated voltage Un and can be
Unbalance V Th
set within the range: 2% to 10% Un, in 1% steps.
NOTE: 0% =symmetrical and balanced system
Control threshold of the V microinterr counter.
V microinterr.
The value is given as a percentage of rated voltage Un and can be
Th
set within the range: 10% to 95% Un, in 5% steps
Control threshold of the Spike counter.
V Spike
The value is given as a percentage of Un and can be set within the
Threshold
range: 105% to 125% Un, in 5% steps
Sags
Menu with the control parameters of the voltage sags
Swells
Menu with the control parameters of the voltage swells
The submenu, which becomes available by enabling the harmonic
Harmonics
current and/or voltage analysis, allows the harmonic control
parameters to be configured
ABB | SACE Emax 2
Default
Off
Off
Off
85 % Un
110 % Un
3 % Un
95 % Un
105 % Un
Continued on the next page
Ekip Touch - Measurements