>690V version IEC circuit-
breakers
>635V version UL circuit-
breakers
169 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Positioning of anchor plates for Terminals FL
The anchor plates must be positioned as indicated in the figure.
Figure 107
>690V disconnectors and circuit-breakers are available in the following configurations:
Circuit-breaker
Voltage
E1.2/E9
800 V
E2.2/E9/E10
800/900/1000 V
E4.2/E9/E10/E12
800/900/1000/1150/1200 V
E6.2/E9
800/900 V
Mandatory provision with front terminals (F) and high terminal covers (HTC)
(1)
(2)
Mandatory provision with positionable rear terminals (HR/VR) and phase separators (PB)
Insulating protections are mandatory for >690 V fixed versions of E2.2, E4.2 and E6.2.
(3)
Details about assembling insulating protections are available at http://www.abb.com/abblibrary/
DownloadCenter/, especially in the kit sheet 1SDH001000r0746.
>635V disconnectors and circuit-breakers are available in the following configurations:
Circuit-breaker
E4.2H-A/E
With insulating protections
(1)
Details about assembling insulating protections are available at http://www.abb.com/abblibrary/
DownloadCenter/, especially in the kit sheet 1SDH001000r0746.
Voltage
730V
ABB | SACE Emax 2
Bus Bracing
Bus Bracing
Version
F
- W
(1)
(2)
F
- W
(3)
F
(3)
- W
F
(3)
- W
Version
F
(1)
Mechanical characteristics
3 - Installation