ABB SACE Emax 2 Series Operating Instructions Manual page 127

Low voltage air circuit-breaker
Table of Contents

Advertisement

124 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Sags Menu
All the thresholds are given as a percentage of rated voltage Un and can be set from 10% to 95% Un, in
5% steps.
All the times are given in seconds and can be set within the range: 0.04 s to 60 s, in variable steps
Parameter
Description
V sag Th Short Control threshold of Sags Short counter
Minimum duration of sag below the Short threshold to validate
V sag dur Short
the count of the Sags Short counter
V sag Th
Control threshold of Sags Middle counter
Middle
V sag dur
Minimum duration of sag below the Middle threshold to validate
Middle
the count of the Sags Middle counter
V sag Th Long
Control threshold of Sags Long counter
Minimum duration of sag below the Long threshold to validate
V sag dur Long
the count of the Sags Long counter
NOTE: Ekip Touch accepts changes to the parameters subject to compliance with the
following limitations: V sag dur Long ≥ V sag dur Middle ≥ V sag dur Short
Swells Menu (Swell)
All the thresholds are given as a percentage of rated voltage Un and can be set from 105% to 125% Un, in
5% steps.
All the times are given in seconds and can be set within the range: 0.04 s to 60 s, in variable steps
Parameter
Description
V swell Th
Control threshold of the Swell Short counter
Short
V swell dur
Minimum duration of swell above the Short threshold to validate
Short
the count of the Swell Short counter
V swell Th Long Control threshold of the Swells Long counter
V swell dur
Minimum duration of swell above the Long threshold to validate
Long
the count of the Swells Long counter
NOTE: Ekip Touch accepts changes to the parameters subject to compliance with the
following limitations: V sag dur Long ≥ V sag dur Middle ≥ V sag dur Short
Harmonics (Current and Voltage)
All the thresholds are given as a percentage and can be set within the range: 5% to 20% (total THD) or: 3%
to 10% (single harmonics) in 1% steps.
Menu
Parameter
THD
Threshold
Current
Single
harmonic th
THD
Threshold
Voltage
Single
harmonic th
Description
Control threshold of the THD Voltages counter
Control threshold of the single harmonics counters of
the voltages
Control threshold of the THD Current counter
Control threshold of the single harmonics counters of
the currents
ABB | SACE Emax 2
Default
10 % Un
0,8 s
45 % Un
0,8 s
95 % Un
0,8 s
Default
125 % Un
0,8 s
105 % Un
0,8 s
Default
5 %
5 %
5 %
5 %
Ekip Touch - Measurements
5 - Network Analyzer