Remote Link configurations Regarding the Link functions, the following further parameters are available:
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote Link information Regarding the Link functions, the following further parameters are available:
239 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Parameter
Description
Permits (Enabled ARP) the periodic generation of a
Gratuitous ARP message, used by Ekip Connect to rapidly
Disable Gratuitous ARP
find the modules via Ethernet scan without knowing the IP
address beforehand
Password protected
Enables the writing operations performed via the network
access
to be protected by a password (Request password)
With access protected by enabled password, this is the
Password Modbus TCP
password to use before each writing session
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(1)
the parameter can only be changed via system bus in the remote configuration
(2)
Parameter
Description
Link Actor (1÷15)
IP address of each actor (from 1 to 15)
Configuration parameters of the configurable states:
• selection of actor (actor from 1 to 15) which activates the
Remote Programmable
programmable status
Status (A÷D)
• event of the actor that determines change of
programmable status
Configuration parameters of the words:
Remote Status word
• selection of actor (actor from 1 to 15) from which the
(A÷D)
word status is taken
• selection of the taken word
Active (Passive diagnosis) or deactivated (No diagnosis)
Diagnostic
cabled selectivity diagnosis
Diagnostic check
30 s, 1 min, 10 min, 60 min diagnosis frequency intervals
timeout
available, if activated
Configuration of hardware selectivity (Only HW) or
Zone Selectivity Type
hardware and logic (Mixed)
Interactive mask for selecting selectivity to be sent also
Repeat Configuration
to the upper levels (even if not active in the programmed
mask
device)
communication:
Information
Description
HW and Boot version
General module information
Flash CRC status and
Information about the correctness of the SW in the module
result
Ekip Link status
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server
State of synchronism with SNTP server
Synchronization
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1558 status
Master Active) or absence (PTP Master but Passive) of a higher level
master
Information
Line Congruency detection
Remote Programmable Status
Remote Status Word
Logic Zone Selectivity
Description
Information about the state and inconsistency of HW and logic
selectivity (state and type of selectivity inconsistent)
Status (true/false) of remote programmable statuses A, B, C and
D
Value of remote programmable Words A, B, C, D
Logic selectivity states (inputs and outputs)
ABB | SACE Emax 2
Default
ARP Enabled
Standard
mode
Local access
.
(2)
Default
0.0.0.0
Actor 1
None
None
1 global
No
Diagnostic
30 seconds
HW only
0x0000
External electronic accessories
9 - Ekip Link