Environmental Conditions - ABB SACE Emax 2 Series Operating Instructions Manual

Low voltage air circuit-breaker
Table of Contents

Advertisement

3 - Environmental conditions

Installation environment Install the circuit-breaker in a dry environment, without dust or corrosive acids, and so that it is not subject
Temperatures of the
installation environment
Particular weather conditions The circuit breaker is designed to operate in particularly difficult industrial environments.
Dusty environments It is recommended to install the circuit breaker in suitably ventilated switchgear where penetration by
Vibration The circuit-breaker is insensitive to mechanical or electromagnetic vibrations that meet the following
7 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
to shock or vibration.
If this is not possible, mount the circuit-breaker in a compartment protecting it adequately.
For the dimensions to be considered for installation, see the chapter "3 - Installation" on page 166 where
the references for following information can be found:
• minimum installation volumes of the circuit-breakers and derived versions in a cell
• overall dimensions of the circuit-breakers and the fixed parts
• drilling of mounting holes
• drilling of the cell door
The mechanical and electrical characteristics are guaranteed between -25 ° C and +70 ° C, -13 °F e +158 °F.
It was tested according to:
• IEC 60068-2-1: endurance at low temperatures
• IEC 60068-2-2: hot dry climate
• IEC 60068-2-30: hot humid climate
• IEC 60068-2-52 severity 2: saline mist atmosphere
• IEC 60947 (pollution level ≤ 3)
• IEC60721-3-6 class 6C3
• IEC60721-3-3 class 3C2
NOTE: the circuit-breaker is suitable for installation in environments with saline concentrations
no higher than 10 mg/m3.
dust is minimized.
In case of dusty environments (dust> 1 mg/m3) second level maintenance procedures must be followed.
standards:
• IEC 60068-2-6 a) From 1 to 13 Hz with movement equal to 1 mm - 0.04 in b) From 13 to 100 Hz with
constant acceleration equal to 0.7 g - 0.025 lbs
• Shipping Registers' specifications: RINA, BV, GL, ABS, LRs, DNV
ABB | SACE Emax 2
Circuit-breakers E1.2-E2.2-E4.2-E6.2
3 - Environmental conditions

Advertisement

Table of Contents
loading

Table of Contents