Ips Interface Protections - ABB SACE Emax 2 Series Operating Instructions Manual

Low voltage air circuit-breaker
Table of Contents

Advertisement

5 - IPS Interface protections

Description The IPS Interface protection function allows faults to be managed in installations which are able to
Protection 59.S1 [ANSI 59S1] The protection sends a TRIP command if the maximum mean value of the three line-to-line voltages,
Protection V DIR [ANSI 27VD] If the positive sequence measured by the Trip unit exceeds or falls below threshold Upos (depending on
Protection V INV [ANSI 59VI] If the negative sequence measured by the Trip unit exceeds or falls below threshold Uneg, the
145 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
function thanks to the energy produced by renewable and local energy sources, especially the absence of
power supply, e.g. caused by a fault on the MV voltage side.
The function is available for all the Ekip Hi-Touch Trip units.
All the parameters and measurements of the function are available via Ekip Connect; however, the Trip
unit allows protection 59 S1, V DIR, V INV and control thresholds Voltage stability , Frequency stability and
F W1 to be set, as described below.
IMPORTANT: consult the Technical catalog or White paper of the function for full details
(page 15, 19).
calculated in a 10-minute floating menu, exceeds the threshold for longer than the set time.
The Protections-Advanced menu includes the protection submenu in which the parameters can be
entered:
Parameter
Description
Activates/deactivates the protection and its availability in the
Enable
parameters menu
Activates/deactivates transmission of the open command: if disabled,
Trip Enable
the alarm and exceedance of protection time are only managed as
information
Establishes the value that activates the protection.
Threshold
The value is given as both absolute value (V) and relative value (Un) and
can be set within the range: 1 Un to 1.3 Un in 0.05 Un steps
This is the trip time of the protection; the value is given in seconds and
Time
can be set within a range: 3 s to 999 s, in 3 s steps
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or
communication via system bus (page 86).
the direction set), the corresponding alarm will be activated (no TRIP).The Protections-Advanced menu
includes the protection submenu in which the parameters can be entered:
Parameter
Description
Activates/deactivates the control threshold of the parameters and their
Enable
availability in the menu
Defines whether sequence monitoring is performed after the
Direction
measured sequence has dropped (Down) or been exceeded (Up)
Establishes the value that activates the alarm.
Threshold
The value is given as both absolute value (V) and relative value (Un) and
can be set within the range: 0.1 Un to 1.5 Un in 0.05 Un steps
corresponding alarm will be activated (no TRIP).
The Protections-Advanced menu includes the protection submenu in which the parameters can be
entered:
Parameter
Description
Activates/deactivates monitoring of the parameters and their
Enable
availability in the menu
Establishes the value that activates the alarm. The value is given as
Threshold
both absolute value (V) and relative value (Un) and can be set within the
range: 0.05 Un to 0.5 Un in 0.05 Un steps
ABB | SACE Emax 2
Default
Off
Off
1,1 Un
3 s
Default
Off
Down
0,8 Un
Default
Off
0,05 Un
Ekip Touch - Additional functions
5 - IPS Interface protections