Synchrocheck With regard to closing the interconnection switch, the Ekip Synchrocheck module recognizes and
Programmable Functions and
Commands
92 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
reports whether there are synchronism conditions between two independent voltage sources (example:
generator + grid).
A description of the module, the protection function and performance is given in the chapter dedicated
to the modules (page 247).
Eight commands are available, with activation that can be programmed on the basis of signals or events.
Distributed among different Ekip Touch menus, the commands are:
Name
Description
External Trip
Sends a TRIP command
Trip RESET
Reset of the trip signal
Turn on SET B
Changes the protections set, from Set A to Set B
It activates 2I protection, if configured for this
2I Mode
function
RESET Energy
Resets the energy meters
YO Command
Sends an open command
YC Command
Sends a close command
Changes the configuration, from Remote to
LOCAL Switch On
Local
Signaling RESET
Reset the contacts of the signalling modules
the MOE-E storage command must be present
(1)
Parameters
Each command provides two programming parameters:
Parameter
Description
Event or several command activation events (up to eight, in AND
Function
or OR logic configuration). The Custom configuration can be
programmed via Ekip Connect.
This is the minimum time the expected event must be present in
Delay
order to activate the command; the value is given in seconds and
can be set within a range: 0 s to 100 s, in 0.1 s steps
IMPORTANT: the commands are sent if all the operating conditions expected by the unit
are present (connections, power supplies, alarms, etc.)
Path (page)
Advanced - Functions
(47)
Advanced - Functions -
2I Menu (62)
Measurements - Energy
(48)
Settings - Functions (
49)
(1)
Settings - Modules
- Functions (49)
Ekip Touch - Protections
9 - Additional protections and functions
ABB | SACE Emax 2
Default
Deactivated
0 s