5 - List of alarms and signals

LED view
Ekip Dip continuously monitors its own operating condition and that of all the devices to which it is connected. All the signals are available
with the front LEDs. The protection LEDs provide information with various combinations of lighting and flashing, while the power-on LED, as
described on page 22, indicates the power-on conditions of the trip unit.
NOTE: the number of LEDs depends on the version of Ekip Dip (LI, LSI, LSIG).
Summary table of LED signals
The following table summarises the signals available with the protection LEDs and the operations to be carried out in response to alarms or fault
conditions signalled.
Slow flashing
Type of Information
(0.5Hz)
Colour and LED
All R
Internal configuration
error
.
(5)
Trip coil disconnected
or trip command failed
Current sensors
x
disconnected
Rating Plug error
Protection delay
Temperature alarm
(1)
Pre-alarm L
Trip
(2)
Hardware Trip
(3)
Installation error
Parameter error
Circuit-breaker state
not defined or in error
Error on Local Bus
Maintenance alarm
Software
incompatibility
Low battery (during
self-test)
(4)
The temperature alarm is signalled by lighting of the protection L and I red LEDs.
(1)
The last trip can also be displayed with trip unit off, by pressing the iTest key.
(2)
The Hardware Trip is signalled by lighting of the pre-alarm L yellow LED and the protection I red led.
(3)
Five flashes when self-test is started up
(4)
Error present with one of the three flashing options displayed alongside.
(5)
Key to LED colours
The above table lists the colors of the LEDs, to be interpreted as follows:
• R = red LED (alarm LED L, S, I, G).
• G = yellow LED (pre-alarm LED L).
NOTE: for further details refer to the table listing the components of the interface, available on page 21.
32 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Fast flashing (2 Hz)
All
R
G
All R
R+G
(single)
x
x
x
x
x
On and fixed
All
R
G
All R
R+G
(single)
x
x
x
x
x
x
x
ABB | SACE Emax 2
ABB | SACE Emax 2
3
2 flashes
flashes
every 2 s
every
3 s
G
All R
G
G
X
x
x
x
x
x
Continued on the next page
4
flashes
every
HELP
4 s
G
A
B
B
B+E
C
C
C
C
B
E
D
B
x
F
F
G
H
Ekip Dip