58 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Function
S2 protection functions in the same way as S protection: if the current of one or more phases exceeds
threshold I5 for longer than time t5, the protection activates and sends a TRIP command.
S2
NOTE: unlike S protection, S2 protection only has one fixed time trip curve and has no thermal
memory
It is independent of S protection, thus thresholds and functions of the two protections can be programmed
so as to take advantage of different plant solutions (example: signaling with S and open command with
S2 or vice versa, or both S and S2 for signaling or tripping).
I
To check and simulate the trip times in relation to all the parameters, please consult:
• the summary table of the protections with the calculation formulas (page 95)
• the graph with trip curve (page 101)
Parameter
Description
Activates/deactivates the protection and its availability in the
Enable
parameters menu.
Activates/deactivates transmission of the open command. If
Trip Enable
disabled, the alarm and exceedance of protection time are only
managed as information.
Establishes the value that activates the protection and
contributes towards calculating the trip time.
Threshold I5
The value is given as both absolute value (A) and relative value (In)
and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
This is the trip time of the protection.
Time t5
The value is given in seconds and can be set within the range:
0.05 s to 0.8 s, in 0.01 s steps
Activates/deactivates the function and selectivity time availability
on the display (page 83)
ZoneSelectivity
This is the trip time of the protection with the zone selectivity
function activated and selectivity input not present (page 83)
Selectivity time
The value is given in seconds and can be set within the range:
0.04 s to 0.2 s, in 0.01 s steps
Activates/deactivates the function and availability of the
StartUp enable
associated parameters on the display (page 86)
Protection threshold valid during Startup time, in the conditions
StartUp
in which the function is activated (page 86)
Threshold
The value is given as both absolute value (A) and relative value (In)
and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
This is the time for which the StartUp threshold remains
activated, as calculated from the moment the activation
StartUp Time
Threshold is exceeded (page 86)
The value is given in seconds and can be set within the range: 0.1
s to 30 s, in 0.01 s steps
Limitations and additional functions
• threshold I5 must be higher than threshold I1 (if S2 protection is activated)
• the block functions and type of selectivity can also be accessed by means of the service connector
(via Ekip Connect) or communication via system bus (page 85)
• with CB in UL standard configuration, the maximum value of t5 is 400 ms
NOTE: if at least two of the selectivity S, S2, I, 2I and MCR
are enabled, the input and output are shared with the OR
function; it is sufficient that even a selectivity is activated to
stimulate inputs and outputs
ABB | SACE Emax 2
Default
OFF
ON
2 In
0,05 s
OFF
0,04 s
OFF
2 In
0.1 s